This is a Demo Server. Data inside this system is only for test purpose.
 

Simulation of the heater test room defined by EN 442 standard and virtual testing og different type of heaters

dc.contributor.advisor İlken, Zafer en
dc.contributor.author Erdoğmuş, Abdullah Berkan
dc.date.accessioned 2023-11-16T12:13:27Z
dc.date.available 2023-11-16T12:13:27Z
dc.date.issued 2011 en
dc.description Thesis (Doctoral)--Izmir Institute of Technology, Mechanical Engineering, Izmir, 2011 en
dc.description Includes bibliographical references (leaves: 166-169) en
dc.description xix, 180 leaves en
dc.description.abstract Heat outputs of radiators are determined experimentally in specific conditions. Many standards have been developed to identify test conditions. EN442 standard specifies test room properties, temperature measurements and heat output calculations for radiators. In this study, the heat dissipation capabilities of three different panel radiators were determined by using numerical methods. The height and length of the tested radiators were 600 mm and 1000 mm, respectively. An experimental study was conducted in the standard test room in order to determine boundary conditions for computational study and verify numerical results. Tests were carried out in three different operating conditions. Twelve measurements were performed in each condition when test room reached steady state. Turbulent typed air flow in the test room and water flow inside the tested radiators were simulated. Temperature and velocity contours in virtual test room are also investigated in this study. Non uniform temperature distribution on the front surface of tested radiators was observed. It is seen that the symmetricity in velocity contours is distorted by using more complex radiator models and increasing excess temperature. The difference between experimental and computational heat output fluctuates between 0.4% and 13.6% for the simplest model, 3.4% and 11.1% for the second radiator, 4.5% and 12.9% for most complicated model investigated in this study. Good results are obtained for the excess temperature of 50oC and 60oC. For the lowest excess temperature, results are also in acceptable range. The study shows that computational methods can be applicable in the design of new heater types. en
dc.identifier.uri http://standard-demo.gcris.com/handle/123456789/6323
dc.language.iso en en_US
dc.publisher Izmir Institute of Technology en
dc.rights info:eu-repo/semantics/openAccess en_US
dc.subject.lcsh Heat engineering--Research en
dc.subject.lcsh Heat engineering--Standarts en
dc.subject.lcsh Radiators en
dc.subject.lcsh Heat--Transmission en
dc.title Simulation of the heater test room defined by EN 442 standard and virtual testing og different type of heaters en_US
dc.type Doctoral Thesis en_US
dspace.entity.type Publication
gdc.description.department Mechanical Engineering en_US
gdc.description.publicationcategory Tez en_US
gdc.oaire.accepatencedate 2011-01-01
gdc.oaire.diamondjournal false
gdc.oaire.impulse 0
gdc.oaire.influence 2.9837197E-9
gdc.oaire.influencealt 0
gdc.oaire.isgreen true
gdc.oaire.keywords Mechanical Engineering
gdc.oaire.keywords Makine Mühendisliği
gdc.oaire.popularity 7.325455E-10
gdc.oaire.popularityalt 0.0
gdc.oaire.publicfunded false

Files

Collections